Black dipstick sensor calibration
The black dipstick sensor comes factory-calibrated. Use this procedure only when it needs recalibration. The two stages measure the sensor in air and fully immersed. Use the matching black dipstick control box. For routine setup, see the installation guide.
Before you start
Have a soft cloth and a container of water from the pool or spa ready. Use enough water to cover both sensing areas of the dipstick while keeping the cable connection dry. Close the manual stop valve during calibration.
Enter calibration mode and take the readings
- Start with the sensor unplugged. Switch the control box off and wait for the power light to go out. Unplug the sensor, then switch the box on. After about five seconds the green light should give two short flashes every two seconds.
- Connect the clean, fully dry sensor. Plug it in while those two short flashes are repeating. The invitation lasts about one minute. When the light flashes rapidly, hold the sensor dry and still for about ten seconds, until the flash pattern changes.
- Immerse both sensing areas. When you see two longer flashes every second, lower the dipstick into the water until both sensing areas are covered. Keep it still and leave the cable connection dry.
- Wait for confirmation. A steady green light for about two seconds followed by even installer-mode flashes means the readings were saved. Leave the sensor wet until you are ready to position it.
- Refit and test. Refit the sensor, reopen the manual stop valve and set the sensor height in installer mode. Then check that the solenoid opens when the sensor is dry and closes when it is put back in water.
If calibration fails
Three short flashes every two seconds indicate a failed calibration. Filling is disabled for that startup. Switch off, wait for the power light to go out, dry the sensor completely and repeat from the first step. If the light pattern differs or calibration fails again, keep the manual stop valve closed and contact WaterLeveller support.